The method of judging the failure of thermocouple input

According to the wiring diagram of the meter, the correct wiring is connected. After the power is turned on, the meter first displays the thermocouple index number of the meter, and then displays the range of the meter. The digital tube of the lower row of the meter is then used to display the set temperature. The upper row of the meter displays the measured temperature.
If the digital display of the upper row of the meter is not the temperature of the heating element, and the status of “over”, “0000”, or “000” is displayed, indicating that the input part of the instrument is malfunctioning, the following test should be performed:
a) Remove the thermocouple from the input of the instrument thermocouple and short-circuit the thermocouple input using any wire. When the power is on, the digital display on the upper row of the instrument is about room temperature, indicating that the thermocouple's internal connection is open, and the same type of thermocouple should be replaced. If it is still the above-mentioned condition, it means that the meter's input terminal is damaged during the transportation process, and the meter must be replaced.
b) Remove the thermocouple of the above-mentioned fault meter and replace it with a thermocouple connected to the meter with the same kind of index number running next to it. After the power is turned on, the upper-line digital tube of the original fault meter shows the temperature of the heating element, indicating the thermocouple. Open the internal connection, replace the same type of thermocouple. If it is still the above-mentioned situation, it means that the meter's input terminal is damaged during the transportation process, and the meter should be replaced.
c) Remove the faulty thermocouple from the meter, use a multimeter to measure ohms (r)*1, and measure the two ends of the thermocouple with a multimeter. If the multimeter shows a large resistance, Thermocouple internal connection open circuit, replace the same type of thermocouple. Otherwise there is a certain resistance, indicating that there is a problem with the input of the instrument, and the instrument should be replaced.
d) According to the wiring diagram of the meter, the wiring is correct. If the meter is powered on, the digital tube on the meter shows a negative value, indicating that the thermocouple “+” and “―” connected to the meter are connected incorrectly. Just change it again.
e) Correct wiring When the instrument is running, the temperature displayed on the digital tube on the upper line of the instrument is different from the actual measured temperature by 30c~60c. The difference is even greater, indicating that the meter's index number is wrong with the thermocouple's index number. According to the thermocouple index b, s, k, e and other thermocouple temperature (oc) and millivolt (mv) value of the relationship between the same temperature (oc), the resulting millivolt value (mv )b The smallest division number, the smallest s division number, the larger k division number, and the largest e division number, are distinguished by this principle.

Naipu ZG series pumps are cantilevered,horizontal,centrifugal slurry pumps. They are used international advanced solid-liquid two-phase flow theory and were designed using the Minimum-Wear Principle. The flow parts of this pumps are suitable for the flow of state media for it's set shape, which reduces hydraulic loss of eddy and impact, both in pump and along the pipeline; so reduced friction of flow parts, lower noise and vibration of the pump translates into improved hydraulic efficiency.

Typical Applications---

Electric Power
Constructional Material
Mine Coal
Coal washing
Sand Reclamation

Sugar Beet

NP-ZG Slurry Pump Construction Component

Construction Drawing1

Main Part Number At The Drawing
 

1 Coupling
2 Shaft
3 Bearing Housing
4 Disassembly Ring
5 Expeller
6 Rear Liner Plate
7 Volute Casing
8 Impeller
9 Front Liner Plate
10 Front Casing
11 Rear Casing
12 Stuffing Box
13 Water Seal
14 Base
15 Support


Materials of Construction
 

 

VOLUTE

IMPELLERS

BASE

EXPELLER

EXPELLER RING

SHAFT SLEEVE

SEALS

Standard

High Chrome Alloy

High Chrome Alloy

 Cast Iron

Chrome Alloy
or
SG Iron

Chrome Alloy
or
SG Iron

SG Iron

Natural Rubber

Options

SG Iron

SG Iron

Mild Steel
Fabricated

SG Iron

SG Iron

 EN56C
Ferralium
Hasteloy C
Ceramic
Stellite
Chrome Oxide

Nordel
Neoprene
Viton
Butyl
EPDM


 ZG SLURRY PUMP SELECTION CHART
Selection chart

     Note:Approximate performance for clear water,to be used for primary selection only.


ZG SLURRY PUMP PERFORMANCE PARAMETERS


Performance Parameters




ZG High Efficiency Slurry Pump

ZG High Efficiency Slurry Pump, High Efficiency Slurry Pump, Ah Slurry Pump, High Head Slurry Pump

Shijiazhuang Naipu Pump Co., Ltd. , https://www.naipu-pump.com